Digital Meter Relay PSM-04D Series

- Small case in DIN size [48mm (W) x 24 mm (H) x 66mm (D)]
- Front panel operating digital scaling
- Hi-Lo comparison output (relay output)
- Analog output built in (4 to 20mA)
- RoHS compliant
■Measurement Input
| Input Signal Source | 2-wire type various linear sensors and converters |
|---|---|
| Input Method | Single end input (isolated from power supply) |
| Input Resistance | 20Ω: I input range, 2-wire type various linear sensors and converters |
| Allowable Over Input | ±110mA: I input range |
| Scaling Method | Digital scaling method by key switch input |
| Scaling Range | Zero scale setting range: ±9999 Full scale setting range: zero scale setting value ±10000 |
| A-D Conversion Method | Double integral technique with zero correction |
| NMRR | 40dB standard (2.5 times/second, 50Hz) |
| Measurement Accuracy | ±0.1% of FS ± 1 digit Ta=+23℃±5℃ 35 to 85%RH, one year |
| Temperature Drift | ±100ppm of FS/℃ Ta=0℃ to +50℃ |
| Warm-up Time | 5 minutes |
| Sampling Rate | Selected and set from one of 10, 5, 2.5, 1 time/second |
■Display
| Number of Displayed Digits | ±4 digits displayed (±9999 displayed) | |
|---|---|---|
| Display Range | For the portion of arbitrary 10000 digits within ±9999 display | |
| Indicator | Height of character 8mm, 7 segments red LED | |
| Display Rate | Selected and set from one of 10, 5, 2.5, 1, 0.5 time/second | |
| Polarity Display | "-" is displayed for minus only | |
| Overflow Display | Overflow of input | Display blinks at Input ≥ +110% FS Input ≤ -10% FS |
| Overflow of display | Display blinks at Display value > +9999 Display value < -9999 |
|
| Decimal point display | 40dB standard (2.5 times/second, 50Hz) | |
| Measurement Accuracy | Can light up at arbitrary digit by key switch input | |
| Zero Suppress | "0" display of upper digits of decimal point display can be suppressed | |
| Last Digit [0] Fixed Display | Display with 0 power digit of 10 fixed to "0" is available | |
■Comparison
| Comparison Value Setting Method | Digital setting method by key switch |
|---|---|
| Comparison Value Setting Range | -9999 to +9999 digits |
| Comparison Value Setting Resolution | 1 digit |
| Hysteresis Setting Range | 1 to 9999 digits |
| Hysteresis Setting Resolution | 1 digit |
| Comparison Method | Individual comparison method The setting value of CTN1 and 2 can be set individually. For comparison mode, "H" and "L" are available, and when "H" is set, upper comparison operation is set, and when "L" is set, lower comparison operation is set. For both of CTN 1 and 2, hysteresis can be set individually. |
| Comparison Operation | CNT1="H" measurement value ≥ CNT1 setting value: relay and LED for CNT1 are turned ON CNT1="L" measurement value CNT1 setting value: relay and LED for CNT1 are turned ON CNT2="H" measurement value ≥ CNT2 setting value: relay and LED for CNT2 are turned ON CNT2="L" measurement value CNT2 setting value: relay and LED for CNT2 are turned ON |
| Comparison Output | Relay contact output Type of contact: 1 make contact (a contact) Contact capacity: DC 30V / 1A, AC 125V / 0.3A (resistance load) Lifetime of contact: 100,000 times or more (at 1,800 times/h opening and closing) Mechanical lifetime: 50,000,000 times or more |
■Analog Output
| Analog Output | Displayed value supported |
|---|---|
| Zero scale setting value corresponds to analog zero output | |
| Full scale setting value corresponds to analog full output | |
| Output Accuracy | ±0.5%FS |
| Resolution | Approximately 10,000 |
| Load Resistance | 4 to 20mA range 300Ω or less |
■Electric Supply Source
| Voltage | DC 24V ± 15%(DC 20.4V to DC 27.6V) |
|---|---|
| Power Consumption | Approximately 2.5W (sensor output current = 25A, CNT1, 2 = ON, -88.88 display) |
■Power Supply for Sensor
| OutputVoltage | DC 24V ± 10%(DC 21.6V to DC 26.4V) (Ta=23℃ ± 5℃) |
|---|---|
| Output Current | 25mA max |
| Temperature Drift | 250ppm/℃ standard (Ta=0 to +50℃) |
■Environment
| Operation Temperature | 0 to +55℃ |
|---|---|
| Operation Relative Humidity | 35 to 85%RH(no dew condensation) |
| Storage Temperature | -20 to +70℃ |
■Other
| Terminal Block for I/O Connection | Terminal block for connecting strip wire SMKDS1,5 made by Phoenix Contact |
|---|---|
| Backup Memory | Each setting data is backed up by EEPROM Number of writings: approximately 1 million times, number of storage years: approximately 10 years |
| Noise Resistance (EMC Directive) | EN61326: planned to be adapted in 1997 |
| Withstand Voltage | AC 500V, one minute, (power supply vs input, live part collectively vs case) |
| Insulation Resistance | 100MΩ or more (initial value: measured at DC 500 mega, power supply vs input, live part collectively vs case) |
| Oscillation Resistance (Performance) | 10 to 55 Hz, width of oscillation 1.5mm, 2 hours for X, Y and Z direction each |
| Impact Resistance (Performance) | 294m/s2 (Approximately 30G) 3 times for 6 directions of X, Y and Z each |
| External DiameterSize | 24H×48W×66D(mm) |
| Weight | Approximately 55g |
| Case | Made of plastic mold |